Fault Catalog

Every fault: method, raw capture, bus state, and what distinguishes it from the others.

Baseline for all comparisons is a healthy three-node bus at 125 kbit/s.


Baseline (healthy)

can0  036   [1]  AA
can0  037   [1]  AA
can0  038   [1]  AA
can0  036   [1]  AA
can0  037   [1]  AA
can0  038   [1]  AA
can0: <NOARP,UP,LOWER_UP,ECHO> mtu 16 qdisc pfifo_fast state UP mode DEFAULT group default qlen 10
    link/can
    can state ERROR-ACTIVE (berr-counter tx 0 rx 0)
          bitrate 125000 sample-point 0.875
          tq 125 prop-seg 6 phase-seg1 7 phase-seg2 2 sjw 1
          gs_usb: tseg1 6..16 tseg2 2..8 sjw 1
          clock 48000000
          re-started bus-errors arbit-lost error-warn error-pass bus-off
          0          0          0          0          0          0

All three IDs present. ERROR-ACTIVE, all counters zero.


Fault 1 — Device in DFU mode

Discovered: accidentally, while flipping the termination switch.

Symptom:

$ candump can0
SIOCGIFINDEX: No such device

The interface disappeared entirely. Nothing had been unplugged.

Diagnosis: the device was still enumerated — but as something else.

BUSID  VID:PID    DEVICE                 STATE
7-2    0483:df11  DFU in FS Mode         Not shared

VID:PID had changed from 1d50:606f (canable2, gs_usb) to 0483:df11 — an STM32 in Device Firmware Update mode. The boot-mode switch sits directly beside the R120 termination switch and had been bumped.

Root cause: boot-mode switch in the wrong position.

Fix: flip it back, replug to force re-enumeration, re-attach to WSL2, bring the interface up.

Why it's worth cataloguing: the device was physically connected, successfully enumerated, visible to the OS, and completely unable to do its job. That present-but-not-functional shape is the same signature as a wedged USB-serial adapter — the port exists, lsusb lists it, a device node sits in /dev, nothing works.

A diagnostic habit that stops at "is it connected?" returns a false negative here. The question has to be: connected as what, and answering?


Fault 2 — Degraded bus wire

Discovered: accidentally, after repeatedly loosening and re-tightening screw terminals while adding a third conductor.

Symptom:

can0  037   [1]  AA
can0  037   [1]  AA
can0  037   [1]  AA

Node 2 present and perfect. Node 1 absent entirely — not intermittent, not corrupted, gone.

Diagnosis, cheapest test first:

Test Cost Result Eliminated
Check Node 1's serial output Free — window already open Still printing Node 1: sent on schedule Power, firmware crash, upload failure
Move the monitor's tap from Node 1's terminal to Node 2's ~1 min No change, still only 037 Listener-side connection
Replace both bus wires ~2 min Both IDs return —

The second test returned no change, which felt like a dead end and wasn't: it eliminated the entire listener-side hypothesis and proved Node 1's frames weren't reaching the bus at all, making the monitor's position irrelevant.

Root cause: a wire that carried signal when first installed and stopped after being unscrewed, re-seated, and clamped alongside a second conductor several times. Likely a fatigued strand inside the insulation, or one that backed out enough to lose contact under the clamp.

Fix: replaced both bus wires.

can0  036   [1]  AA
can0  037   [1]  AA
can0  036   [1]  AA
can0  037   [1]  AA

Why it's worth cataloguing: the wire looked perfect. This is the signature of strain-relief and connector-wear failure on real robots — intermittent, correlated with handling or arm pose, invisible on inspection. It's also the class of fault a power cycle appears to "fix," because jostling the hardware momentarily reseats a marginal contact. Those recur weeks later and nobody connects them to the earlier incident.


Fault 3 — Node disconnect

Method: with all three nodes running, physically disconnect one node's CAN-H wire while candump runs.

Capture:

can0  036   [1]  AA
can0  037   [1]  AA
can0  036   [1]  AA
can0  037   [1]  AA
can0  036   [1]  AA
can0  037   [1]  AA

Bus state during the fault:

can0: <NOARP,UP,LOWER_UP,ECHO> mtu 16 qdisc pfifo_fast state UP mode DEFAULT group default qlen 10
    link/can
    can state ERROR-ACTIVE (berr-counter tx 0 rx 0)
          bitrate 125000 sample-point 0.875
          tq 125 prop-seg 6 phase-seg1 7 phase-seg2 2 sjw 1
          gs_usb: tseg1 6..16 tseg2 2..8 sjw 1
          clock 48000000
          re-started bus-errors arbit-lost error-warn error-pass bus-off
          0          0          0          0          0          0

Result: the disconnected node vanished from candump. The bus stayed ERROR-ACTIVE with zero tx/rx errors and no bus-errors. Completely clean.

Signature: one ID missing, bus metrics unchanged. This is a local fault — that device, its connector, or its controller. Nothing is corrupting the shared medium.

In a real fleet this is the cheapest and most useful distinction available: it tells you whether to go look at one joint or at the whole harness.


Fault 4 — Duplicate CAN ID

Method: flash two nodes with the same CAN ID (0x036) but different data bytes, so both transmit identical arbitration fields.

Why this differs from a collision: CAN arbitration is resolved electrically — a dominant bit overrides a recessive one, the loser backs off and retries, no data lost. That works when IDs differ. With identical IDs and different data, neither node loses arbitration; the conflict surfaces later, in the data field.

Capture:

can0  036   [1]  AA
can0  036   [1]  AA
can0  036   [1]  55
can0  036   [1]  AA
can0  036   [1]  55
can0  036   [1]  AA

Bus state during the fault:

can0: <NOARP,UP,LOWER_UP,ECHO> mtu 16 qdisc pfifo_fast state UP mode DEFAULT group default qlen 10
    link/can
    can state ERROR-ACTIVE (berr-counter tx 18 rx 0)
          bitrate 125000 sample-point 0.875
          tq 125 prop-seg 6 phase-seg1 7 phase-seg2 2 sjw 1
          gs_usb: tseg1 6..16 tseg2 2..8 sjw 1
          clock 48000000
          re-started bus-errors arbit-lost error-warn error-pass bus-off
          0          7          0          0          0          0

Result: transmit error counter climbed to 18, bus-errors to 7. The state remained ERROR-ACTIVE — the errors accumulated but never crossed the error-passive threshold.

The counter that didn't move matters: arbit-lost stayed at 0. Both nodes transmit the same identifier, so neither loses arbitration to the other. The intuitive guess — "duplicate IDs cause arbitration loss" — is wrong, and the counters say so directly.

Signature vs. fault 3: both produce "expected traffic is missing." Fault 3 leaves the bus completely clean. Fault 4 shows the controller actively detecting transmission errors while nodes are still trying to send. Same surface symptom, opposite counter behavior.


Fault 5 — Missing and wrong-value termination

Method: two variants —

  1. Termination removed from one physical end entirely
  2. Termination replaced with an effective 60Ω (two 120Ω resistors in parallel)

Capture — termination removed:

can0  036   [1]  AA
can0  037   [1]  AA
can0  038   [1]  AA
can0  036   [1]  AA
can0  037   [1]  AA
can0  038   [1]  AA

Capture — 60Ω substituted:

can0  036   [1]  AA
can0  037   [1]  AA
can0  038   [1]  AA
can0  036   [1]  AA
can0  037   [1]  AA
can0  038   [1]  AA

Bus state (checked after both variants; neither produced a change):

can0: <NOARP,UP,LOWER_UP,ECHO> mtu 16 qdisc pfifo_fast state UP mode DEFAULT group default qlen 10
    link/can
    can state ERROR-ACTIVE (berr-counter tx 0 rx 0)
          bitrate 125000 sample-point 0.875
          tq 125 prop-seg 6 phase-seg1 7 phase-seg2 2 sjw 1
          gs_usb: tseg1 6..16 tseg2 2..8 sjw 1
          clock 48000000
          re-started bus-errors arbit-lost error-warn error-pass bus-off
          0          0          0          0          0          0

Result: null

Neither variant caused frame loss or moved any counter. The interface stayed ERROR-ACTIVE throughout, with all three nodes transmitting normally.

This is documented as-is rather than escalated until something broke.

The bus here is a few feet of bench wiring at 125 kbit/s. Signal reflections that would destroy a long deployed harness are simply below the failure threshold at this scale and bitrate. The experiment exposed a limitation of benchtop reproduction, not a property of the protocol.

That's a useful finding in its own right: some physical-layer faults require the physical scale of the real system before their consequences appear. It's precisely why termination problems surface in deployed robots and not in testing.


Summary table

Fault candump symptom Bus state Counters Distinguishing signal
Node disconnect One ID missing ERROR-ACTIVE All zero Missing traffic, bus completely clean
Duplicate ID One ID, alternating data bytes ERROR-ACTIVE berr tx 18, bus-errors 7, arbit-lost 0 Errors accumulating while nodes still transmit
Bad termination No change ERROR-ACTIVE All zero No software-visible signal at this bus length
Bad wire / connector One ID missing ERROR-ACTIVE All zero Indistinguishable from node disconnect by counters — separated by a physical swap test
Device in DFU mode Interface gone entirely n/a n/a Enumerates under a different VID:PID

What the table actually shows

Two pairs are not distinguishable by counters alone:

  • Node disconnect vs. bad wire produce identical signatures. Both are one ID missing on a clean bus. Separating them required a physical test — checking the node's serial output to confirm it was still transmitting, then moving the monitor's tap point.
  • Bad termination vs. healthy are identical at this scale.

So the counters aren't a fault classifier. They narrow the search space, and they're decisive for fault 4, but the resolution comes from combining them with cheap physical tests:

  • candump — is expected traffic present?
  • Bus state and counters — is the shared medium unhappy, or just quiet?
  • Node serial output — is the sender still running?
  • A controlled physical change — does the fault follow the hardware?

That's not a lookup table. It's a progressively narrower search — which is closer to how real robot debugging actually works.